If the transformers are used in the parallel operation or
used in the polyphase circuit, the
polarities of primary and secondary terminals must be known at any instant. Due
to the potential difference between two
points, the current can from the high voltage point to low voltage point. The polarity
is nothing but it describes the direction of the current flow. The dot
convention is used to identify the polarity of two windings.
- If a current enters to the dotted terminal of one winding,
the polarity of the voltage on the secondary winding will be positive at the dotted
terminal.
- If current leaves to
the dotted terminal of one winding, the polarity
of the voltage on the secondary winding
will be negative at the dotted terminal.
Assume the primary side of the transformer at a particular instant of time the polarity is A1
which is positive with respect to A2. In this case, if the voltmeter reading V
= E1 + E2 means additive polarity, then B1 is negative and B2 is positive at
any instant of time A1 is positive and A2 is negative.
Replace dot marks at either positive polarity terminals or
negative polarity terminals on both sides.
During this polarity test, if the voltmeter reads sum of two
EMFs, the secondary side terminals should assign as opposite polarity with
respect to assumed primary polarity.
If voltmeter reading is V = E1 – E2 means negative polarity
(difference of two EMFs), then the secondary
side terminal should be assigned with the same
polarity as assumed primary side.
This test can be easily implemented on a low voltage range of the transformer and cannot
be used for a high voltage range of
transformer.
DC kick test:
This method is used for low voltage range transformer as
well as a high voltage transformer. In this
method, the transformer is excited with
DC supply. This excitation is not continuously. It is momentarily excitation.
If you give continuous excitation of DC supply than it is possible
to damage the transformer because very high current will flow in the primary. So,
never excite transformer with DC supply. If you want to excite transformer with
DC, excite HV winding because it has a high
resistance compared to LV winding.
When DC voltage is applied to the primary winding terminal A1
which is positive with respect to A2. If the switch
is closed and opened and momentary supply is given to primary winding of the transformer. In this case, the galvanometer observed
a kick.
If the kick is in the forward
direction, secondary side terminals should be assigned as the same polarity of primary winding terminals. If dot
notation is to be applied, a pair of similar terminals should be assigned with
dot marks.
If the kick is in the backward
direction, secondary side terminals should be assigned as the opposite polarity of primary winding terminals.
If dot notation is to be applied, a pair of dissimilar terminals should be
assigned with dot marks.
Vary helpful information. it really helped me.
ReplyDeletePower Transformers in India | Transformer Manufacturer in India
Really really helpful
ReplyDeletechina cem-1 front supplier
ReplyDeletechina cem-1 front supplier
ReplyDeleteMost reliable post that gives great information about transformer.
ReplyDeleteServo Voltage Stabilizer Manufacturers | Servo Controlled Voltage Stabilizer | Voltage Stabilizer | Automatic Voltage Controllers
Nice post regaring stabilizer concept. To get Industrial electrical & power equipment ( stabilizer & transformer)with high quality premium features like Servo Controlled Voltage Stabilizer, Automatic Voltage Controllers, Air Cooled Servo Stabilizer Manufacturers, Automatic Voltage Stabilizer Transformer Manufacturers, Deal with us.
ReplyDeletethanks a lot..for giving a good information
ReplyDeleteVery great post. It's really very informative. I am hoping you write again very soon.And if you need more information about AC Voltmeter (Three Phase) you can check out my page also. It will help you.
ReplyDelete